Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/07/2012 | ELECTRIC - RECONNECT | Denied | PROVIDE EXT. LADDER FOR ROOF ACCESS | |
| 03/26/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED WIRING ON ROOF, TERMINATE PROPERLY IN APPROVED J-BOX AND COVER |
|
| 02/21/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MC CABLE INTO 4'S BOX IN FRONT NOT SUPPORTED OR CONNECTED PROPERLY 2) SWITCH IN BATHROOM NOT INSTALLED PROPERLY, NO COVER PLATE 3) MC CABLES/CONDUITS NOT SUPPORTED PER CODE AT SUB PANEL-SUPPORT TO STRUCTURE. SEAL HOLES AND USE PROPER CABLE CONNECTORS 4) OUTSIDE PANEL MISSING DEAD FRONT COVER 5) HAVE ELECTRICIAN CHECK OUT ROOF AND MAKE REPAIRS AS NECESSARY, HAVE LADDER FOR NEXT INSPECTION 6) USE QUALIFIED OR LICENSED ELECTRICIAN |