Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2014 | FIRE SPKLR - FINAL | Approved | ||
| 04/28/2014 | FIRE SPKLR - FINAL | Cancelled | Water accident | |
| 04/23/2014 | FIRE SPKLR - FINAL | Denied | 2 inch drain test 80-70-85 1. Add a sign adove the FDC over the height of the wall so that FDC can be located 2. Light blocking sprinkler head in break room move light or lower sprinkler head. 3. Classroom #7 sprinkler heads covered in storage rooms 4. Fire bell failed 5. Need lock out on break for fire bell |