Permit: T12CM00380

Parcel: 135074470


Addresses:

1470 S EASTSIDE LP

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
09/23/2013 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
09/18/2013 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/18/2013 PLUMBING - SEWER HCS CONNECT Denied SUPPORT 8" WYE. CORRECT SETTLING. PROVIDE MIN 1/4" PER FOOT SLOPE ON 4". PROVIDE A TWO-WAY CLEANOUT @ BUILDING.
09/16/2013 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/16/2013 PLUMBING - SEWER HCS CONNECT Denied TRANSITION GLUE OR COUPLING REQUIRED @ ABS TO PVC. 4" SWEEP REQ ON VERT TO HORIZ. TRACER WIRE REQUIRED. PROVIDE MIN 1/4" FOR FOOT SLOPE. TWO-WAY CLEAN OUT.