Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T12CM00380
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2013 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
09/18/2013 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/18/2013 | PLUMBING - SEWER HCS CONNECT | Denied | SUPPORT 8" WYE. CORRECT SETTLING. PROVIDE MIN 1/4" PER FOOT SLOPE ON 4". PROVIDE A TWO-WAY CLEANOUT @ BUILDING. | |
09/16/2013 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/16/2013 | PLUMBING - SEWER HCS CONNECT | Denied | TRANSITION GLUE OR COUPLING REQUIRED @ ABS TO PVC. 4" SWEEP REQ ON VERT TO HORIZ. TRACER WIRE REQUIRED. PROVIDE MIN 1/4" FOR FOOT SLOPE. TWO-WAY CLEAN OUT. |