Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM00376
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2013 | FIRE - FINAL | Approved | ||
05/23/2013 | FIRE - FINAL | Partial Approval | Okay to install fixtures and stock shelves. Front parking lot hydrant 5"cap needs to be facing towards building (east not west). Turn fire lane signs to face direction of traffic travel. Label outside of riser room door "RISER ROOM". Mount all fire extinguishers Label fire alarm panels and nec panel with panel location and circuit number. Install F.D. Key box mounted by front doors eye height or approx. 5' off of grade. |
|
02/19/2013 | FIRE - FINAL | Denied | Need to check make up air for hot water heater room no vents on door, walls or ceciling. |