Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2013 | FIRE SPKLR - FINAL | Approved | ||
| 02/19/2013 | FIRE SPKLR - FINAL | Partial Approval | Fire pump testing done and passed Label test valve for fire pump with a sign "TEST HEADER or FIRE PUMP TEST HEADER". Need hardware on riser room door exiting to the outside, FD must be able to make entry from the outside. Need to label riser room door with a sign "RISER ROOM". Writing on cal plate needs to be etched on not labeled. Need to get make up air fixed in the fire pump room, damper did not open when fire pump testing was completed. |