Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T12CM00376

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2013 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/19/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/19/2013 MECHANICAL - INTERMEDIATE Denied PROVIDE LISTED PARTS INSTALLED AS SPECIFIED BY MANUFACTURER
06/13/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/07/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/06/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/24/2013 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/30/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/30/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection SUPPORT CASE DRAINS, LEAVE TOO KICKOFF. SUPPORT REFER LINES AT CASES; VERICAL MIDSTORY REQUIRES APPROVED CLAMPS. ZIP TIES SHOWN FOR TRAPEZE ONLY SEE DETAIL R2 #1.
TOILET ROOM FANS SHALL RUN CONTINUOUS PER SCH. M3. MAKE-UP AIR FOR HOODS TO BE CONTINUOUS OR INTERLOCKED.
COMPLETE METAL FAB ABOVE HOOD #1, PROVIDE SMOKE TEST.
SINGLE WALL WH VENT REQ SILICONE. PER M3 #6. BVENT TERMINATION SHALL BE MIN OF 8' FROM SIDE WALL. 1FGC 503.6.4
NEED CAPTURE AND CONTAINMENT TEST ALSO AIR DUET SMOKE DETECTORS AND AIR BAL.
PROTECT ALL EXPOSED PLASTIC
11/27/2012 MECHANICAL - INTERMEDIATE Partial Approval RT-15: RESTROOMS; RT-13 PERSONNEL OFFICES OK TO INSULATE DUCT WORK
11/21/2012 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/22/2012 MECHANICAL - INTERMEDIATE Partial Approval SW AREA ROUND DUCT SEALED SE AREA