Permit: T12CM00376

Parcel: 136100930


Addresses:

2711 S HOUGHTON RD

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
05/02/2013 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
01/04/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
12/17/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*3 WATER DRAINAGE AREAS IN SITE WALLS OK TO GROUT AND CAP PROGRESS AREAS
12/12/2012 REINFORCED MASONRY PRE-GROUT Partial Approval PALLATE STORAGE AREAS- TOPPED OUT AT 8' ABOVE STEM WALL: OK TO GROUT AND CAP
12/10/2012 REINFORCED MASONRY PRE-GROUT Partial Approval N&S PLANTERS AT TOP OUT OK TO GROUT AND CAP
12/04/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 8'8" GL: H/6-7 OK TO GROUT PROGRESS AREAS

* EAST RETAINING (2) WING WALLS AT 4' NW PLANTER OK TO GROUT/ POR PROGRESS AREA
12/03/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
11/20/2012 REINFORCED MASONRY PRE-GROUT Partial Approval TREASH COMPACTOR WALLS-TOPPED OUT AT 10' OK TO GROUT AND CAP
11/19/2012 REINFORCED MASONRY PRE-GROUT Partial Approval TRASH WALLS 2ND LIFT 4'8" OK TO GROUT PROGRESS AREAS
11/14/2012 REINFORCED MASONRY PRE-GROUT Partial Approval TRASH COMPACTOR WALLS AT 48" GL; 1.5-3.5 OK TO GROUT
10/29/2012 REINFORCED MASONRY PRE-GROUT Partial Approval PILASTERS (6) AT 12'6"-LOADING DOCK AREA-OK TO GROUT PROGRESS AREAS
10/23/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
10/22/2012 REINFORCED MASONRY PRE-GROUT Partial Approval LOADING DOCK WALLS TOPPED OUT 6 PILASTERS AT 4' 8" -SITE WALLS AT 5' 4" SOUTH WALL APPROX 320'
10/16/2012 REINFORCED MASONRY PRE-GROUT Partial Approval 15 PILASTERS-TOPPED OUT AT 16' OK TO GROUT PROGRESS AREAS
10/15/2012 REINFORCED MASONRY PRE-GROUT Partial Approval 15 PILASTERS AT 12' OK TO GROUT PROGRESS AREAS CMU WALL AT 26'-28' TOP OUT GL: K / 3.5-5 OK TO GROUT
10/12/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALL AT 28' GL: K/ 2.75-4.5 OK TO GROUT PROGRESS AREA
10/11/2012 REINFORCED MASONRY PRE-GROUT Partial Approval 15 EXTERIOR PILASTERS; N,S,W WALLS AT 8'- OK TO GROUT PROGRESS AREAS
10/10/2012 REINFORCED MASONRY PRE-GROUT Partial Approval 14 PILASTERS AT 48" LIFT; (N,S,W WALLS) CMU WALL AT 26' GL: L/3.5-4.5 AT 28' GL; L/4.5-5.4- OK TO GROUT PROGRESS AREAS
10/09/2012 REINFORCED MASONRY PRE-GROUT Partial Approval cmu walls at 20'8"; gl:2.2/k-l*
GL:K-L 2.2-3;K/4-5.4;WALLS AT 26'8;GL 5.4/H-K H/5.4-8- OK TO GROUT PROGRESS AREAS
10/08/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALL AT 26'8"9TOP-OUT) GL:L/1-2.2 2.2/K-L OK TO GROUT
10/05/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 20'8"; GL: L/1.5-2.2; 2.2/L-K; K/2.2-3.25 5.4/H-K; H/5.4-6.5- OK TO GROUT PROGRESS AREAS
*NOTE; GL: K/3-5.4-NOT TO BE GROUTED; SPACING BETWEEN STEEL IN BEDS AND CMU WALL INCORRECT; ROOF STEEL EXPANSIONS MAY CAUSE WALL TO CRACK AREA IN QUESTION TO BE INSPECTED BY kLIENFELDER SPECIAL STEEL INSPECTOR.
10/04/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALL AT 16'8"; GL:H/5.4-8
NOTE: CORNER OF CMU WALL AT GL: L/2.2 (20'8") CORNER DISPLACED DUT TO STEEL EXPANSION- DISPLACEMENT APPROX. 1/2"-MORTAR BROKEN REPAIR TO BE EFFECTED BEFORE AREA CAN BE GROUTED
10/03/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 24'8" GL:C/5.3-7; CMU WALL AT 26'8" GL: C/1-6-2.6 CMU WALL AT 16'8"- GL: K/3-5.4; 5.4/H-K-OK TO GROUT PROGRESS AREAS
10/02/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
10/01/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 8'8
-12'8" GL: K/2.2-5.4 5.4/H-K; H/5.4-8; CMU WALL AT 16'8"-20'8"
GL:C/1.6-2.6; AT 16'8"- GL: 2.6/AC OK TO GROUT PROGRESS AREA
09/27/2012 REINFORCED MASONRY PRE-GROUT Partial Approval SMU WALLS AT 12'8"-16'8" GL: A/1.6-2.6
09/26/2012 REINFORCED MASONRY PRE-GROUT Partial Approval GL: 1.6/A-C; CMU WALLS AT 4'8"-8'8" GL:H/ 5.4-8 OK TO GROUT PROGRESS AREAS

NOTE: GL:C/2.4-IN BED FALLS ON CONTROL JOINT-RFI TO BE SUBMITTED FOR CLEARANCE TO GROUT AFFECTED AREA
09/25/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 12'8"-16' GL:C/5.3-7.2 5.4/C-B; 5.3-4.2; 16'8"-18; GL C/3.2-4.2
09/24/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 12'8'-16'8" GL:C/5.3-7
8'8 "-12'8" GL C/1.6-2.7; 4'8"-8'8" GL 1-6/A-C 4'8"-8'8" GL L/2.2-3.5
OK TO GROUT PROGRESS AREAS
09/20/2012 REINFORCED MASONRY PRE-GROUT Partial Approval 7 PIERS AT 8' AFFE GL: A/1.6-3.2; CMU WALLS AT 56" AFFE GL:2.2/K-L; K/2.2-5.4 5.4/H-K OK TO GROUT PROGRESS AREAS
09/19/2012 REINFORCED MASONRY PRE-GROUT Partial Approval EAST ADN WEST WALLS AS NOTED IN SPECIAL INSPECTORS (ADAM) NOTES
09/18/2012 REINFORCED MASONRY PRE-GROUT Partial Approval
09/17/2012 REINFORCED MASONRY PRE-GROUT Partial Approval LOCATIONS 1-5 AS NOTED ON SPECIAL INSP REPORT
09/13/2012 REINFORCED MASONRY PRE-GROUT Partial Approval MASONRY PREGROUT..CMU WALLS AT 24'8" 26' (TOPOUT) GL: 1/D.2-G.1;STEM WALL AT C/2.3-3.2; A-C/1.6-5.3 AT 0-48"; C/5.3-6.8-4'8"-8'-8"- OK TO GROUT PROGRESS AREAS
09/12/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 28'0" GL: C/6.8-7.2 WALL AT 28'- 8/C-F.2: 24'8'-26'8": GL: F.2-H/8 WALL- 12'8" 16'8 GL ;/1-2.2: AT 24'8". GL;C/1-2.5 1/C-D
09/11/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
09/10/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 20'8-24'8 GL: C/6-B-8: 8/C-E.7: WALL AT 16'8-20'8- 8/F.7-H OK TO GROUT
09/06/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 12'-16: GL:L/1.5-1;1/L-K STEM WALL AT GL: L/1.2-2.2; CMU WALLS AT 16'-20'; GL:8/C-F.6 C/7-8 OK TO GROUT PROGRESS AREAS
09/05/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 2'8"-16'8": GL C/1-2.6; 1/A-K OK TO GROUT PROGRESS AREAS
09/04/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 8'8"-12'8"; GL 1/C-J.5
4'8"-8'8"; 1/J.5-L; L/1-1.5 12'"; GL:8/C-H; C/6-8- OK TO GROUT PROGRESS AREAS
08/31/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 8'-12'8, GL:8/C-H,C/6.9-8 AT 4' :GL:J.1-L/1: L/1-1.7 OK TO GROUT
08/30/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 8'-12' GL:1/C-K.5; OK TO POUR PROGRESS AREAS

C8/WF FOOTING GL: C.5/2.6-3.2 OK TO POUR PROGRESS AREAS
08/29/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 8'-12' GL: 8/C-H; C/6.-8. OK TO GROUT PROGRESS AREAS
08/28/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT GL: 2.5-3.2/C
STEMWALL; STEM WALL 1/J.5-1; L/1-2.2; O"-48" GL: 1/C-K.5; 8/F.5-H OK TO GROUT PROGRESS AREA
08/24/2012 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 48" AFFE
GL: 8/C-F.7; B-C/5.3 ; 5.3-8/C OK TO GROUT PROGRESS AREAS
STEM WALL-GL: 1/C J.5- OK TO GROUT
08/22/2012 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
08/17/2012 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
08/16/2012 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/14/2012 REINFORCED MASONRY PRE-GROUT Partial Approval STEM WALL AT 16"-GL:8/C-G.5; C/3.2-8 MISSING CONTROL JOINTS- TO BE CUT AND VERIFIED BY SUPERINTENDENT