Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL LUGGED CIRCUIT 4 20 AMP 2) PROTECT ALL EXPOSED ROMEX REAR STORAGE ROOMS. ADDED CIRCUITS TO PANEL FROM PHYSICAL DAMAGE 3) SECURE ALL ROMEX 8" FROM BOXES STORAGE ROOMS 4) NOTE 3 FROM PREVIOUS |
|
| 03/01/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING COVER PLATES AND CLEAN EXCESS PAINT FROM RECEPTS 2) RECEPTS IN COMBUSTIBLES NEED ARC SHIELDS 3) WIRING IN STORAGE ROOM NOT CODE COMPLIANT-NUMEROUS ITEMS 4) INSTALL SMOKE DETECTORS PER INSTRUCTIONS AND IN ALL BEDROOMS 5) RECEPT COMING OUT OF WALL 6) PROTECT BULB IN CLOSETS |