Permit: T12CM00344

Parcel: 125042500


Addresses:

2127 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/30/2012 BUILDING - FINAL Approved
04/27/2012 BUILDING - FINAL Denied 1) ALL ITEMS, EXCEPT WORKING CLEARANCES 110.26
04/26/2012 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) FINISH ITEMS 1,3,4/1,2 AS DISCUSSED WITH TIM
04/24/2012 BUILDING - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) GATE LOCKED-PER MSG "BACK ALLEY"
2) RESCHEDULE INSPECTION
04/23/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAINTAIN WORKING SPACE 110.26
2) GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64-?
3) LABEL COMBINDER PANEL BREAKERS AND INVERTERS TO MATCH (PERMANENT)
4) LABEL INVERTERS 690.17
5) PLEASE OPEN INVERTERS TO INSPECT
ROOF:
1) NO MORE THAN 360 DEGREE IN RACEWAY RUNS
2) USE ALL APPROVED PARTS FOR "SOLAR CITY" WEEB SYSTEM
3) SUPPORT LOOSE PV AND GROUNDING CONDUCTORS UP UNDER ARRAYS