| 05/02/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/01/2012 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/25/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONLY 1 CONDUCTOR PER LUG TERMINATION 2) LABEL SERVICE DISCONNECT 3) CLEAN SURFACES UNDER GROUND LUGS 250.12 4) IDENTIFY GROUNDED CONDUCTOR AT LUG 5) PROTECT CONDUCTORS 300.4 AND 352.46 (PVC) 6) NEED APPROVED MOUNTING HARDWARE, NOT DRY WALL SCREWS 7) IDENTIFY EQUIPMENT GROUNDING CONDUCTOR AT LUG |