Date Description Inspector Results Comments
05/02/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/01/2012 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
04/25/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONLY 1 CONDUCTOR PER LUG TERMINATION
2) LABEL SERVICE DISCONNECT
3) CLEAN SURFACES UNDER GROUND LUGS 250.12
4) IDENTIFY GROUNDED CONDUCTOR AT LUG
5) PROTECT CONDUCTORS 300.4 AND 352.46 (PVC)
6) NEED APPROVED MOUNTING HARDWARE, NOT DRY WALL SCREWS