Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/15/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/15/2013 | ELECTRIC - FINAL | Partial Approval | - MAIN BREAKERS NEED PERFORMANCE TESTING ON SITE PER 230.95 N.E.C. AND PER MANU F. INSTRUCTIONS - COMPLETE LABELING OF EQUIP & PANEL SCHEDULES - BOND BUSHINGS AT DISCONNECT SWITCHES WITH CONCENTRIC RO'S - OVER 250 VENTS - PER 250 N.E.C. |