Permit: T12CM00289

Parcel: 114476000

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/17/2012 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
04/13/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) P3005.2.9 2006 IRC INSTALL 2 WAY CLEANOUT SHOWN FOR GREY BLDG DRIAN
2) 3" DRAIN REQUIRES 3" CLEANOUT
3) REMOVE ROCKS TOUCHING PIPE THAT ARE LARGER THAN 5/8"
4) PIPING SHALL BE LAID ON A FIRM COMPACTED BED WITH ONLY BELL HOLES UNDER JOINTS P-2605.1/2604.1/2604.3 AND 2503.5.1