Permit: T12CM00270

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T12CM00270

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2012 ELECTRIC - PROGRESS Approved OK PER ELECTRIC FINAL
09/04/2012 ELECTRIC - PROGRESS Cancelled IVRS - RI canceled
08/08/2012 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*1) PANEL "SEGDL" DOES NOT FEED "DRGC-L" ARE 4/0 CONDUCTORS NEW?
2) PANEL LABEL TO BE ON OUTSIDE COVER
3) NEED LABELING PER 705.10
4) WHERE IS GROUNDING ELECTRODE CONDUCTOR TAP TERMINATED TO?
06/15/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
MEET CONTRACTOR TO DISCUSS WORKING CLEAR BULBS