Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T12CM00270
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2012 | ELECTRIC - INTERMEDIATE | Approved | OK PER ELECTRIC FINAL | |
08/08/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*1) PANEL "SEGDL" DOES NOT FEED "DRGC-L" ARE 4/0 CONDUCTORS NEW? 2) PANEL LABEL TO BE ON OUTSIDE COVER 3) NEED LABELING PER 705.10 4) WHERE IS GROUNDING ELECTRODE CONDUCTOR TAP TERMINATED TO? |