Permit: T12CM00259

Parcel: 136087210

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/09/2012 BUILDING - FINAL Approved IVRS - Inspection :*
03/02/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PAPERWORK AND PRINT MISSING
2) MIDDLE STRING TO NORTH STRING PIPE STRAPS LOOSE
3) PANEL MISISNG LABEL TO SUB PANEL AND 2 K.O. SEALS MISSING
4) 3/4 PIPE FROM PANEL TO DISCONNECT MISSING STRAP AND FROM METER BASE TO ROOF MISSING STRAP
5) VERIFY SUB PANEL NOT OVER LOADED FROM ENGINEER