Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/02/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PAPERWORK AND PRINT MISSING 2) MIDDLE STRING TO NORTH STRING PIPE STRAPS LOOSE 3) PANEL MISISNG LABEL TO SUB PANEL AND 2 K.O. SEALS MISSING 4) 3/4 PIPE FROM PANEL TO DISCONNECT MISSING STRAP AND FROM METER BASE TO ROOF MISSING STRAP 5) VERIFY SUB PANEL NOT OVER LOADED FROM ENGINEER |