Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/02/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) USE LISTED MAST BRACE KIT 2) FINISH SUPPORT OF RISER 3) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4) FILL UNUSED OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE PRODUCT 5) PHYSICAL PROTECTION FOR GEC 6) NO MORE THAN 360 DEGREE IN CONDUIT RUN 7) PLEASE VERIFY PERMIT FOR NEW A/C |
|
| 02/28/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) ANSWERED QUESTIONS FOR CROSS OVER 2) ROOF WORK OK |