Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2012 | BUILDING - FINAL | Approved | ||
| 03/28/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND JUMPER ON BOND BUSHING NEEDS TO BE #8 CU MIN. 250.92 AND 690.92 NEC 2) COULD NOT LOCATE PLANS ? |
|
| 03/22/2012 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) THIS INSPECTION IS FOR SERVICE TAP AND PV SYSTEM 2) CALLED CLEARANCE INTO TEP 3) CONTRACTOR WILL REVISE PLAN TO MATCH INSTALL, WILL CALL FOR FINAL |