Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T12CM00249
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/08/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU CANNOT HAVE CLASS 2 LOW VOLTAGE T-STAT WIRE IN A DISCONNECT WITH HIGH VOLTAGE WIRING. USE THE PROPER FITTING TO CONNECT SEAL TITE CONDUIT TO EMT. FOIL TAPE IS NOT TO BE USED AS A FITTING CONDENSATE DRAIN NOT SUPPORTED PROPERLY - RUNS UPHILL UNDER A/C UNIT. PANIT EXPOSED PVC WITH LATEX PAINT. |
|
02/03/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |