Inspection History: MECHANICAL - FINAL

Permit Number - T12CM00249

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/17/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/08/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
YOU CANNOT HAVE CLASS 2 LOW VOLTAGE T-STAT WIRE IN A DISCONNECT WITH HIGH VOLTAGE WIRING.
USE THE PROPER FITTING TO CONNECT SEAL TITE
CONDUIT TO EMT. FOIL TAPE IS NOT TO BE USED AS A FITTING
CONDENSATE DRAIN NOT SUPPORTED PROPERLY - RUNS UPHILL UNDER A/C UNIT. PANIT EXPOSED PVC WITH LATEX PAINT.
02/03/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*