Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T12CM00221
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2012 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/28/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) NEED AIR BALANCE REPORT AND SMOKE DETECTORS INSTALLED |
|
03/19/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) THERE IS NO DUCT SMOKE DETECTION SYSTEM FOR MULTIPLE AIR HANDLING IN A PLENIUM CEILING |