Permit: T12CM00189

Parcel: 11928140C


Addresses:

2410 W 44TH ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T12CM00189

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2012 FRAMING Approved IVRS - Inspection :*
03/09/2012 FRAMING Not ready for Inspection IVRS - Inspection :*
1) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION, IF NO COMPLIANCE
03/08/2012 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSED PVC TO BE SCHEDULE 80 PER CITY OF TUCSON ORDINANCE
2) LB AT SERVICE PED. LOOSE, IMPROPER FITTING, SHOULD BE CLOSE NIPPLE LOCK NUTS, BOND BUSHING 110.3 NEC
3) INSTALL GROUNDING ELECTRODE SYSTEM AT RWEMOTE PV ARRAY AS REQUIRED FOR SEPERATE STRUCTURE 250.32 NEC
4) 2P 15 AMP CKT BRKER. AT SERVICE AS CALLED OUT ON PLAN. PERMANENT LABEL ON BRKR, NO MARKER PEN
5) PVC CONDUITS AT INVERTER ? TO HAVE PHYSICAL PROTECTION ABOVE GRADE
6) PLANS CALL FOR 4 #10 TO INVERTER FROM ARRAY
7) IS SONORA PLUMBING THE CONTRACTOR ? IF NOT CHANGE CONTRATOR OF RECORD