Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T12CM00189
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2012 | FRAMING | Approved | IVRS - Inspection :* | |
03/09/2012 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION, IF NO COMPLIANCE |
|
03/08/2012 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED PVC TO BE SCHEDULE 80 PER CITY OF TUCSON ORDINANCE 2) LB AT SERVICE PED. LOOSE, IMPROPER FITTING, SHOULD BE CLOSE NIPPLE LOCK NUTS, BOND BUSHING 110.3 NEC 3) INSTALL GROUNDING ELECTRODE SYSTEM AT RWEMOTE PV ARRAY AS REQUIRED FOR SEPERATE STRUCTURE 250.32 NEC 4) 2P 15 AMP CKT BRKER. AT SERVICE AS CALLED OUT ON PLAN. PERMANENT LABEL ON BRKR, NO MARKER PEN 5) PVC CONDUITS AT INVERTER ? TO HAVE PHYSICAL PROTECTION ABOVE GRADE 6) PLANS CALL FOR 4 #10 TO INVERTER FROM ARRAY 7) IS SONORA PLUMBING THE CONTRACTOR ? IF NOT CHANGE CONTRATOR OF RECORD |