Permit: T12CM00168

Parcel: 13409018E


Addresses:

8640 E BROADWAY BL


Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T12CM00168

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
04/12/2013 MECHANICAL - FINAL Partial Approval JUST NEED TEST AND BALANCE REPORT AND RESOLE BACKFLOW ISSUE AT HYBRID UNIT
04/12/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/11/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
04/11/2013 MECHANICAL - FINAL Partial Approval CORRECTIONS AT PO SYSTEM HAVE NOT BEEN MADE: PROPER USE OF FITTINGS & MIN AIR CAP. SUPPORT AIR PIPE LEAKING
1/2 GRATE NEEDED TO MINIMIZE SPLASHING
PROVIDE AIR BALANCE REPORT
PROVIDE PROOF OF APPROVED BACK FLOW PROTECTION FOR HYBRED UNIT INSPECTOR NEEDS A COPY OF DOCUMENTATION
04/10/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
04/01/2013 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/28/2013 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*PROVIDE MAKE-UP AIR FOR HOODS, PLAN SHOWS ONLY 165 CFM OUTSIDE AIR INTO ROOM. STEM 3. PROVIDE AIR BAL REPORT- ALSO SMOKE DETECTOR AND SMOKE CONTAINMENT TEST. NEED TO SEE CASE DRAIN PIPE SUPPORTS AND PIPING SECURE/ SUPPORT REFER LINES AT CASES.