Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T12CM00168
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2013 | MECHANICAL - FINAL | Partial Approval | JUST NEED TEST AND BALANCE REPORT AND RESOLE BACKFLOW ISSUE AT HYBRID UNIT | |
| 04/12/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/11/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/11/2013 | MECHANICAL - FINAL | Partial Approval | CORRECTIONS AT PO SYSTEM HAVE NOT BEEN MADE: PROPER USE OF FITTINGS & MIN AIR CAP. SUPPORT AIR PIPE LEAKING 1/2 GRATE NEEDED TO MINIMIZE SPLASHING PROVIDE AIR BALANCE REPORT PROVIDE PROOF OF APPROVED BACK FLOW PROTECTION FOR HYBRED UNIT INSPECTOR NEEDS A COPY OF DOCUMENTATION |
|
| 04/10/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/01/2013 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/28/2013 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*PROVIDE MAKE-UP AIR FOR HOODS, PLAN SHOWS ONLY 165 CFM OUTSIDE AIR INTO ROOM. STEM 3. PROVIDE AIR BAL REPORT- ALSO SMOKE DETECTOR AND SMOKE CONTAINMENT TEST. NEED TO SEE CASE DRAIN PIPE SUPPORTS AND PIPING SECURE/ SUPPORT REFER LINES AT CASES. |