Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T12CM00168
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2013 | ELECTRIC - ABOVE CEILING | Approved | ||
03/13/2013 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CUSTOMER SERVICE CEILING LITING OK 2. DISCONNECTS FOR DOCK LEVELER OK 3. FLOW & DAMPER OK |
|
03/11/2013 | ELECTRIC - ABOVE CEILING | Partial Approval | 1. PRODUCE AND DAIRY COOLER LIGHTING ONLY JBOXES AND FAN COILS SEALED INSIDE AND ON TOP 2. MEAT COOLER, FREEZER LIGHTING AND FAN COILS OK 3. SALES FLOOR LIFTING ONLY OK 4. PHARMACY LIGHTING ONLY OK 5. GENERALTE GROUNDING AND CONNECTIONS OK 6. COFFINS CASES AND FREEZERS GROUNDING AND MAKE UP OK 7. RACK HOUSE B OK 8. RACK HOUSE A OK 10 COOLING TOWER A OK |