Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12CM00167

Parcel: 140160080

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM00167

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2012 FIRE - FINAL Approved
06/25/2012 FIRE - FINAL Denied 1. Again wording on non-functional egress shall state the following "THIS DOOR BLOCKED" 6 inch letters with a ¾ inch stroke on a contrasting back color.
2. Repair egress exit door on the northwest side of building (rear of building).
06/22/2012 FIRE - FINAL Not ready for Inspection 1. STILL NEED SIGN STATING DOOR IS BLOCKED.
2. STILL NEED ADDRESS ON BUILDING.
3. SPRINKLER FINAL HAS BEEN DONE ALL DEFICIENCIES CORRECTED EXCEPT HEAD IS PAINTED IN OFFICE.
06/20/2012 FIRE - FINAL Denied 1. IFC 1028.6 Panic Hardware on doors is the only devices allowed on egress doors - no slide bolts; flush bolt locks or dead bolt locks.
2. IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts area not permitted. Shall remove bolt lock from front door mounted on the bottom.
3. IFC 504.2 Maintenance of exterior doors and openings. Exterior doors that have been rendered nonfunctional shall be label on the outside with the following: THIS DOOR BLOCKED" 6 inch high lettering ¾" stroke on a contrasting background color.
3. Address numbers need to be posted on the building handout was given.
4. Sprinkler inspections are pass due and 5 year check valve inspections are pass due. THIS WILL HOLD UP YOUR FINAL