Permit: T12CM00167

Parcel: 140160080

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12CM00167

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2012 FIRE SPKLR - FINAL Approved
06/25/2012 FIRE SPKLR - FINAL Denied Replace painted head in bathroom do not try to clead paint off.
06/22/2012 FIRE SPKLR - FINAL Not ready for Inspection 1. SPRINKLER HEAD PAINTED IN BATHROOM.
06/20/2012 FIRE SPKLR - FINAL Denied Correct sprinkler coverage on sales floor northwest side by exit door.
Correct sprinkler cover under roll up door southwest side by bathrooms.
Correct upright coverage north end of building by A/C duct work small dead area.
Remove tape from sprinkler heads in office and bathrooms.