Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/09/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH GROUNDING ELECTRODE SYSTEM + ROOF MAKE-UP |
|
| 02/08/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROTECT CONDUCTOR 300.4 2. GROUNDING ELECTRODE CONDUCTOR IN METAL RACE WAY TO BE BONDED 250.64 (B) 3. VERIFY 25 OTMS OR LESS FOR GROUNDING ELECTRODE SYSTEM 4. SEPERATE GROUNDS + NEUTRALS AT SUB PANEL + REMOVE BOND SCREW 250.24 5. FILL UNUSED OPENING AT BACK PANEL 110.12 6. CLEAN SURFACE UNDER GROUND BAR 250.12 ROOF: 1. PULL OUT DISCONNECT ENCLOSURES CAN NOT BE USED AS JUNCTION BOXES 110.3 (B) 2. PLEASE VERIFY MANUFACTURE LISTING FOR RAIL + MODULE BONDING 3. PARTIAL ROOF |