Permit: T12CM00145

Parcel: 112060030


Addresses:

2654 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T12CM00145

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2012 ELECTRIC - UFER Approved IVRS - Inspection :*
02/08/2012 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROTECT CONDUCTOR 300.4
2. GROUNDING ELECTRODE CONDUCTOR IN METAL RACE WAY TO BE BONDED 250.64 (B)
3. VERIFY 25 OTMS OR LESS FOR GROUNDING ELECTRODE SYSTEM
4. SEPERATE GROUNDS + NEUTRALS AT SUB PANEL + REMOVE BOND SCREW 250.24
5. FILL UNUSED OPENING AT BACK PANEL 110.12
6. CLEAN SURFACE UNDER GROUND BAR 250.12
ROOF:
1. PULL OUT DISCONNECT ENCLOSURES CAN NOT BE USED AS JUNCTION BOXES 110.3 (B)
2. PLEASE VERIFY MANUFACTURE LISTING FOR RAIL + MODULE BONDING
3. PARTIAL ROOF