Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/19/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*MULTIPLE 14 AWG WIRES ON 20AMP BREAKERS -POWER OFF TO WHOLE HOUSE |