Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/02/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STRAPPING MISSING ON 2-3/4 EMT UNDER PANEL 2) #8 GROUND FROM INVERTER TO GROUNDING ELECTRODE MISSING CRIMP 3) 690.17 LABEL ON BREAKER MISSING 4) LB ON METER HAS SCREWS LOOSE 5) 1ST STRING OF PANELS ON ROOF MISSING J-BOX COVER AND STRAP ON 3/4 MORE THAN 10' ON SOUTH SIDE |