Permit: T12CM00051

Parcel: 137055270

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T12CM00051

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2012 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/11/2012 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) ABOVE CEILING NOT PER PLANS-SEE DETAILS
2) PROVIDE SESMIC WIRES AT ALL GRILLS
3) PROVIDE BEADED COLLARS ON ALL REGISTERS
4) NO COMBUSTIBLE MATERIALS IN PLENIUM RATED CEILINGS
5) CONDENSATE NOT PER PLANS