Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PRE SLAB
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2012 | PLUMBING - PRE SLAB | Approved | IVRS - Inspection :* | |
| 08/08/2012 | PLUMBING - PRE SLAB | Not ready for Inspection | PROVIDE A TEST. COPPER SPECIFIED. WASTE MAY NOT BE RESTRICTED IN SIZE AT FLOW CONTROL FITTING. NO SYSTEM VENT MAY BE INSTALLED DOWN STREAM OF FLOW CONTROL VENT. AAV MAY NOT BE USED AT FLOW CONTROL. 2006 UPC REVENT IS REQUIRED TO BE 6" ABOVE FIXTURE FLOOD COVER. WATER SUPPLY PIPING IS UNDER SIZED. SUPPORT ALL PIPING |