Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12CM00032
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2012 | FIRE SPKLR - FINAL | Approved | ||
10/19/2012 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. Need Subcontractor to call in final. | |
10/15/2012 | FIRE SPKLR - FINAL | Denied | 1.) Remove tape on sprinkler head in office 2nd fl #231 2.) Correct sprinkler coverage by exit door (east) #227 3.) Correct sprinkler coverage in office #202 one head is 10' off wall 4.) Install heads over reception desk in lobby #102 as per approved sprinkler plans. 5.) Install sprinkler coverage in office #134 as per approved sprinkler plans. 6.) Install sprinkler coverage in open office area #127 as per approved sprinkler plans. 7.) Remove cover cap on sprinkler head in shower #125. 8.) Install grid ceiling and add sprinkler coverage or add full height walls to deck and then add sprinkler coverage or completely install upright sprinkler coverage throughout 1st floor in supply room #124. 9.) In open office area next to supply room #124, 2 heads to close together need to be 6' apart. 10.) In riser room again as above statement #112 11.) Mount spare head box on wall. |