Permit: T12CM00022

Parcel: 11616287A


Addresses:

845 N MAIN AV


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T12CM00022

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2012 MECHANICAL - HOODS Approved IVRS - Inspection :*
04/17/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 2ND LAYER OF FIRE WRAP OK
04/13/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF FIRE WRAP 2 DUCTS, OK FOR 2ND LAYER
04/12/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) HOOD EXHAUST DUCT NOT SIZED PER PLAN
2) MVA DUCT NOT SIZED PER PLAN
3) CONTRACTOR SAYS HE IS GETTING A SIZE REVISION FROM ENGINEER OF RECORD AND AGREES TO PROCEED AT OWN RISK
4) PROVIDE APPROVED STRAPS ON DUCT WORK (SMACNA)
5) GREASE DUCT SMOKE/LEAK TEST OK, OK TO INSTALL 1ST LAYER FIRE WRAP
04/11/2012 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
04/09/2012 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SPACING BETWEEN DUCT AND TRUSSES, NEED TO SMOKE TEST DUCT
2) MVA NOT SEALED
04/05/2012 MECHANICAL - HOODS Cancelled CANCELLED PER SUB-CONTRACTOR RON ALDRICH #623-518-3908
04/05/2012 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*