Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T12CM00022
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2012 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
04/17/2012 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 2ND LAYER OF FIRE WRAP OK |
|
04/13/2012 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER OF FIRE WRAP 2 DUCTS, OK FOR 2ND LAYER |
|
04/12/2012 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) HOOD EXHAUST DUCT NOT SIZED PER PLAN 2) MVA DUCT NOT SIZED PER PLAN 3) CONTRACTOR SAYS HE IS GETTING A SIZE REVISION FROM ENGINEER OF RECORD AND AGREES TO PROCEED AT OWN RISK 4) PROVIDE APPROVED STRAPS ON DUCT WORK (SMACNA) 5) GREASE DUCT SMOKE/LEAK TEST OK, OK TO INSTALL 1ST LAYER FIRE WRAP |
|
04/11/2012 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
04/09/2012 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE SPACING BETWEEN DUCT AND TRUSSES, NEED TO SMOKE TEST DUCT 2) MVA NOT SEALED |
|
04/05/2012 | MECHANICAL - HOODS | Cancelled | CANCELLED PER SUB-CONTRACTOR RON ALDRICH #623-518-3908 | |
04/05/2012 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* |