Permit: T12CM00022

Parcel: 11616287A


Addresses:

845 N MAIN AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T12CM00022

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/24/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEPTS TO BE GFCI PROTECTED 210.8 (B)
2) SUPPORT M/C CABLE FOR ICE MAKER DOWN BELOW AND ROOF PER CODE
3) PROTECT LFNMC FROM SHARP EDGES
4) PROVIDE DISCONNECTING MEANS ON ROOF FOR ICE MAKER CONDENSOR
5) TIGHTEN LOOSE FITTINGS FOR EXHAUST UNITS