Permit: T12CM00002

Parcel: 138100680


Addresses:

6010 S NOGALES HY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/12/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/06/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE LISTED DEAD FRONT AND LABEL ALL CIRCUITS
2) WHITE HOT LEAD 50 AMP BREAKER MUST BE RED OR BLACK (TAPE OK)
3) PROVIDE 30 AMP SQUARED 'D' BREAKER TYPE AT WATER HEATER IN SUB PANEL
4) SEAL KNOCKOUTS BOTTOM PANEL
5) OVER FUSED BREAKERS FOR WIRE SIZE IN PANEL. ALL BREAKERS MUST MATCH PANEL TYPE
6) PROVIDE PROTECTION PVC INTO WATER HEATER ENCLOSURE