Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T12BU01437
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2013 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
01/31/2013 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1.electric did not shut down all electrical conections inside controll head per manufacturer need to be outside in its own junction box. items that passed 1. gas valve shut off 2. exhaust stays on 3. lines clear blew off caps 4. alarm was activated when hood was tripped . |