Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T12BU01425

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/04/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INTERLOCK MAKE UP AIR WITH EXHAUST FANS. PROVIDE HINGE KITS AT EXHAUSAT FANS. EXTEND GREASE DUCTS TO TOP OF CURBS. PROVIDE A GASKET BETWEEN FAN & CURB. PROVIDE DISCONNECTS AT EXHAUST FANS. OK TO INSTALL FIRE SUPPRESSION SYSTEM