Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2013 | FIRE SPKLR - FINAL | Approved | ||
| 05/08/2013 | FIRE SPKLR - FINAL | Denied | 1. Need test header labeled "TEST HEADER" or "FIRE PUMP TEST HEADER" 2. Need to etch the information on cal plate can not just use maker 3. Need proper information on the fire pump acceptance test paper work the serial number and model numbers did not match for the driver, jockey pump and main controller. 4. Need alarm final |