Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12BU01290
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2013 | FIRE SPKLR - FINAL | Approved | SEE FINAL FOR APARTMENT BUILDING | |
09/26/2013 | FIRE SPKLR - FINAL | Denied | STILL NEED FDC SIGNAGE | |
08/13/2013 | FIRE SPKLR - FINAL | Cancelled | IVRS - RI canceled | |
08/13/2013 | FIRE SPKLR - FINAL | Denied | 1st Floor 1. Patch drywall by fire head at entry to men's room. 2. Golf room,move head away from wall. 3. Add head between mail boxes and leasing office. 4. Install 2 trims at 1 bedroom unit. 5. Patch drywall in 1 bedroom. 6. Hall, replace damaged ceiling tile . 7. Add head in storage. 8. Trim at tanning entry. 3rd floor 1. Trim at electric room. 2. Move ceiling light minimum 4" away from Fire head. 3. Note to painter all heads in entire building will be trimmed so any additional painting will require masking heads and remove masking afterwards. 4. Trash room,patch drywall,Put on fire trim. 5. 2311 adjust kitchen head. 6. 2317 Straighten head bedroom B, 2nd floor: 1. 2214 Patch drywall in closet 2. 2211 missinghead in bedroom 3. 2210 fire trim entry closet. 4. 2209 move head 4" away from bar light. 5. Janitor room masking off head and trim. |
|
08/08/2013 | FIRE SPKLR - FINAL | Partial Approval | 1. Partial for 5th and 6th floor units. 2. Partial for 4th floor. |
|
02/20/2013 | FIRE SPKLR - FINAL | Denied | Cell # 602-628-0320 Tim |