Permit: T12BU01286

Parcel: 10408001C

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12BU01286

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2013 FIRE SPKLR - FINAL Approved
12/18/2012 FIRE SPKLR - FINAL Denied Painted sprinkler heads in the following areas:
1.) Loading dock area by roof ladder
2.) By 3rd column from south wall then 3 more heads on same line going east ward.
3.) By new concentrail A/C unit
4.) By PF Tucson wall
5.) In women's bathroom back north corner
6.) 2nd floor mezzanine taped and painted south wall windows

1.) Straighten sprinkler piping on 2nd floor mezzanine where drops were removed.
2.) Two sprinkler heads to close to each other by the northwest stairs 2nd floor mezzanine and 1st floor southwest corner by the PF Tucson wall
3.) Correct sprinkler coverage in the large storage room 2nd floor and by the stairs going down to 1st floor northeast.
4.) Correct sprinkler coverage in the sun tanning rooms blocked by units x5