Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T12BU00978
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 200 PSI TEST FOR 2 HOURS HEADS MOVED |
|
09/14/2012 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Sprinkler head in unit 905 on 2nd floor needs to be moved at least 4 in. away from wall. 2. Pressure test was good at 70psi. (55psi required) |