Permit: T12BU00978

Parcel: 99999999A


Addresses:

1000 E 22ND ST 09


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T12BU00978

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2012 FIRE SPKLR - OH PIPING & HYDRO Approved 200 PSI TEST FOR 2 HOURS
HEADS MOVED
09/14/2012 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Sprinkler head in unit 905 on 2nd floor needs to be moved at least 4 in. away from wall.
2. Pressure test was good at 70psi. (55psi required)