Permit: T12BU00953

Parcel: 11901051L


Addresses:

3390 S 6TH AV


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T12BU00953

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2012 FIRE - ALARM FINAL Approved
08/23/2012 FIRE - ALARM FINAL Denied While testing flow switches on the sprinkler system I looked over all horn/strobes, need to install horn/strobe in the car stereo shop.
Need to test alarm system, only seen horn/strobes nothing else because troubles still on panel.
08/20/2012 FIRE - ALARM FINAL Denied 1.) 2 TROUBLES ON PANEL CAN NOT TEST WITH TROUBLES SHOWING ON PANEL.
2.) COVER WIRING IN J-BOXES CAN NOT HAVE WIRING HANGING OUT OF BOXES IN RISER ROOM.
3.) NEED LOCK OUTS ON BREAKERS FOR ALARM PANEL AND NACS
4.) LABEL LOCATION AS TO WHERE ELECTRICAL PANEL IN LOCATED INSIDE FACP BOX.