Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12BU00953
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2012 | FIRE - ALARM FINAL | Approved | ||
| 08/23/2012 | FIRE - ALARM FINAL | Denied | While testing flow switches on the sprinkler system I looked over all horn/strobes, need to install horn/strobe in the car stereo shop. Need to test alarm system, only seen horn/strobes nothing else because troubles still on panel. |
|
| 08/20/2012 | FIRE - ALARM FINAL | Denied | 1.) 2 TROUBLES ON PANEL CAN NOT TEST WITH TROUBLES SHOWING ON PANEL. 2.) COVER WIRING IN J-BOXES CAN NOT HAVE WIRING HANGING OUT OF BOXES IN RISER ROOM. 3.) NEED LOCK OUTS ON BREAKERS FOR ALARM PANEL AND NACS 4.) LABEL LOCATION AS TO WHERE ELECTRICAL PANEL IN LOCATED INSIDE FACP BOX. |