Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12BU00942
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2013 | FIRE - ALARM FINAL | Approved | ||
| 03/05/2013 | FIRE - ALARM FINAL | Partial Approval | 1. No troubles showing on FACP 2. Roof top need to test duct smoke detectors x 2 3. All breakers for NAC's and FACP need lock outs |
|
| 02/26/2013 | FIRE - ALARM FINAL | Partial Approval | Roof top need to test duct smoke detectors x 2 Test new flow switches added at the main OS&Y All breakers for NAC's and FACP need lock outs Need date of install on all batteries for NAC's and FACP Correct tamper switches in fire pump room - two tampers for by-pass did not work. |