Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T12BU00942

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2013 FIRE - ALARM FINAL Approved
03/05/2013 FIRE - ALARM FINAL Partial Approval 1. No troubles showing on FACP
2. Roof top need to test duct smoke detectors x 2
3. All breakers for NAC's and FACP need lock outs
02/26/2013 FIRE - ALARM FINAL Partial Approval Roof top need to test duct smoke detectors x 2
Test new flow switches added at the main OS&Y
All breakers for NAC's and FACP need lock outs
Need date of install on all batteries for NAC's and FACP
Correct tamper switches in fire pump room - two tampers for by-pass did not work.