Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12BU00854
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2012 | FIRE - ALARM FINAL | Approved | ||
07/12/2012 | FIRE - ALARM FINAL | Denied | 1.) When testing duct detectors A/C units failed to shut down only the compressors not the fans. 2.) Need to reprogram alarm system so that only reset button is the only thing that resets the A/C units and dampers, can not have silence button resting systems. 3.) At FACP panel need to label all devices as to where they are located by name or map mounted by panel showing each device location by number. 4.) Need a breaker lock out on the fire alarm system in the electrical panel. |