Permit: T12BU00807

Parcel: 137055270

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T12BU00807

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2012 FIRE SPKLR - OH PIPING & HYDRO Approved
08/28/2012 FIRE SPKLR - OH PIPING & HYDRO Denied 1.) ON SITE AT 0830 HRS, NO PRESSURE ON GAUGES.
2.) WRONG WYE CONNECTION USING ONE THAT IS LABEL STANDPIPES, NEED ONE THAT IS LABELED SPRINKLER CONNECTIONS.
3.) CHECK VALVE INSTALLED WRONG, TRUCKS PUMP TO RISER.