Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T12BU00807
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
08/28/2012 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1.) ON SITE AT 0830 HRS, NO PRESSURE ON GAUGES. 2.) WRONG WYE CONNECTION USING ONE THAT IS LABEL STANDPIPES, NEED ONE THAT IS LABELED SPRINKLER CONNECTIONS. 3.) CHECK VALVE INSTALLED WRONG, TRUCKS PUMP TO RISER. |