Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 08/28/2012 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1.) ON SITE AT 0830 HRS, NO PRESSURE ON GAUGES. 2.) WRONG WYE CONNECTION USING ONE THAT IS LABEL STANDPIPES, NEED ONE THAT IS LABELED SPRINKLER CONNECTIONS. 3.) CHECK VALVE INSTALLED WRONG, TRUCKS PUMP TO RISER. |