Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12BU00788
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2013 | FIRE SPKLR - FINAL | Approved | ||
| 03/06/2013 | FIRE SPKLR - FINAL | Partial Approval | Shall change out main OS&Y valve | |
| 03/05/2013 | FIRE SPKLR - FINAL | Partial Approval | 1. Need fire pump test 2. Main OS&Y needs changed 3. No troubles showing on FACP |
|
| 02/26/2013 | FIRE SPKLR - FINAL | Partial Approval | 7th Floor: Ice machine room painted head 6th Floor: Room 629 Painted head 5Th Floor: Ice machine room head 9 foot off wall need to correct 2Nd Floor: In re-fresh room correct sprinkler coverage head to far off wall, maybe need two heads in this room. 1ST Floor head main lobby to close to wall 4 inched min Need heads added to drop ceiling in work out room. Basement parking: Front of elevators need upright coverage above drop ceiling all sides open to the parking garage. Aux/inspector test valves need to be plumb to the sump pump drain hole for testing the new flow switches now and yearly. Need fire pump test done |
|
| 02/13/2013 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. Need heads in 1st floor luggage room and IDF room. 2. Move 2 heads off of wall in Dry Storage Room. |