Permit: T12BU00788

Parcel: 12504079B


Addresses:

1900 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12BU00788

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2013 FIRE SPKLR - FINAL Approved
03/06/2013 FIRE SPKLR - FINAL Partial Approval Shall change out main OS&Y valve
03/05/2013 FIRE SPKLR - FINAL Partial Approval 1. Need fire pump test
2. Main OS&Y needs changed
3. No troubles showing on FACP
02/26/2013 FIRE SPKLR - FINAL Partial Approval 7th Floor:
Ice machine room painted head
6th Floor:
Room 629 Painted head
5Th Floor:
Ice machine room head 9 foot off wall need to correct
2Nd Floor:
In re-fresh room correct sprinkler coverage head to far off wall, maybe need two heads in this room.
1ST Floor head main lobby to close to wall 4 inched min
Need heads added to drop ceiling in work out room.
Basement parking:
Front of elevators need upright coverage above drop ceiling all sides open to the parking garage.
Aux/inspector test valves need to be plumb to the sump pump drain hole for testing the new flow switches now and yearly.
Need fire pump test done
02/13/2013 FIRE SPKLR - FINAL Not ready for Inspection 1. Need heads in 1st floor luggage room and IDF room.
2. Move 2 heads off of wall in Dry Storage Room.