Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 07/16/2012 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. Only one head in 1st floor master bedroom. Plans show two heads. Not sufficient coverage in this area. 2. Plans show two sidewalls under stairs. Only one head present, and its a pendant. Not sufficient coverage. 3. No head, or coverage in bedroom # 3 closet on second floor. Plans show head in closet. |