Permit: T12BU00782

Parcel: 141353910

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T12BU00782

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2012 FIRE SPKLR - OH PIPING & HYDRO Approved
07/16/2012 FIRE SPKLR - OH PIPING & HYDRO Denied 1. Only one head in 1st floor master bedroom. Plans show two heads. Not sufficient coverage in this area.

2. Plans show two sidewalls under stairs. Only one head present, and its a pendant. Not sufficient coverage.

3. No head, or coverage in bedroom # 3 closet on second floor. Plans show head in closet.