Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2013 | FIRE SPKLR - FINAL | Approved | ||
| 02/07/2013 | FIRE SPKLR - FINAL | Denied | 1. Can not have any shut off valves after the water meter that will turn off the sprinkler system, unless when valves are turned off, all domestic water is shut down the same time. 2. If you want the shut off valves in place that turn sprinkler system off only then you will need to install a UL/FM fire alarm monitoring system. This system will need to be installed by an approved plan and permit. |