Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12BU00461
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2013 | FIRE - ALARM FINAL | Approved | Approved - According to Ken Brouillette, Tucson Fire will be working with Maits team and making sure evacuation plans are made and person or persons from TCC knows when lights need to be turned on. | |
12/13/2012 | FIRE - ALARM FINAL | Not ready for Inspection | 1. A AC#3 STILL HAS SAMPLING TUBE IN DUCT NEEDS TO BE PLUGGED. 2. NEED TO WALK ALL WHEN COMPLETE 3. NEED A MORE PERMENANT SOLUTION FOR FIRE PHONE BOXES NEED TO SCRAPE OFF EMERGENCY STICKERS. 4. PER CARL 10 PERCENT TEST NEEDS TO BE DONE TCC WOULD NOT ALLOW IT THEY WERE NOT INFORMED. |
|
11/20/2012 | FIRE - ALARM FINAL | Partial Approval | 0700 hours started 5 min run on alarm system after walking all areas run time was 13 mins 38 secs. Tested 3 of the 4 flow swithes could not get into the office area need to have keyed locked repaired. |
|
11/20/2012 | FIRE - ALARM FINAL | Partial Approval | 1. 24 hour stand-by - Passed 2. Tamper switch northwest - Passed 3. Flow switches - Passed 4. Voice repeat in Spanish - Passed 5. Need to remove all old fire appliances and fire phones. Call for inspection when done. 6. Still need lights to come back up when system is activated. |
|
11/19/2012 | FIRE - ALARM FINAL | Partial Approval | Turned off A/C power to all NAC's and main panel for 24 Hour stand-by battery test - 0730 hrs | |
10/25/2012 | FIRE - ALARM FINAL | Partial Approval | OKAY TO REMOVE OLD FIRE ALARM SYSTEM Per IFC 1006.2 Illumination level shall not be less than 1 foot-candle at walking surface level, but with the exception gives 0.2 foot-candle level provided that the required illumination is automatically restored upon activation of a premises' fire alarm system where such system is provided. Will need to have the alarm system restore the lighting when activated. Will need to have voice repeat notice in Spanish language Can not have any sounds made during any performances that have the same sound as to the alarm system if so, will need to change the alarm sounds. |
|
10/23/2012 | FIRE - ALARM FINAL | Partial Approval | Tested all duct smokes - passed SA-7 Northwest riser tamper failed |