Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2012 | FIRE - KITCHEN EXH HOOD FINAL | Approved | System trip all passed, Red tags removed okay to use deep fryers Still need as bults Advised manager on duty that they will need to step up on cleaning of the equipment and hoods, also found grease soaked towels behind the doors to the deep fryers told manager if there is a leak they need to get it repaired. No leaks were noticed at time of testing. |
|
| 07/03/2012 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Hood #1 passed Hood #2 Cut link electrical failed to shut down - Red tag three fryers not to use until electrical shut down properly. Also will need as bults for changes in the duct work only one 2W nozzle used when plans show two 2W nozzles.(duct is smaller than what's on plans) |
|
| 07/03/2012 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Tested second time still failed same as the first inspection |