Permit: T12BU00369

Parcel: 10511061P


Addresses:

4510 N ORACLE RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12BU00369

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2012 FIRE SPKLR - FINAL Approved level one all done
06/05/2012 FIRE SPKLR - FINAL Denied 1. Need spare heads in boxes
2. Need head wrenches
3. Need FDC caps installed
4. Need to check sprinkler heads in the show cases.
06/04/2012 FIRE SPKLR - FINAL Partial Approval 1. In the accessory room section tape and painted sprinkler covers (level one only).
2. Check all sprinkler cover plates throughout the store some cover plates have paint or tape on the edges possibility keeping the plate on and not letting it drop off and needed (level one only).
04/02/2012 FIRE SPKLR - FINAL Partial Approval Looked at sales area for contractor to install hard lids piping looked good, all areas looked at are marked on approved sprinkler plans.