Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2012 | FIRE SPKLR - FINAL | Approved | level one all done | |
| 06/05/2012 | FIRE SPKLR - FINAL | Denied | 1. Need spare heads in boxes 2. Need head wrenches 3. Need FDC caps installed 4. Need to check sprinkler heads in the show cases. |
|
| 06/04/2012 | FIRE SPKLR - FINAL | Partial Approval | 1. In the accessory room section tape and painted sprinkler covers (level one only). 2. Check all sprinkler cover plates throughout the store some cover plates have paint or tape on the edges possibility keeping the plate on and not letting it drop off and needed (level one only). |
|
| 04/02/2012 | FIRE SPKLR - FINAL | Partial Approval | Looked at sales area for contractor to install hard lids piping looked good, all areas looked at are marked on approved sprinkler plans. |